1. Scope
This specification is applied to VCTF 43Z is heat resistant insulated polyvinyl chloride, oil and heat resistant polyvinyl chloride sheathed flexible cords.
2. Type, conductor size, adaptation standard, rating
Type, conductor size, adaptation standard and rating are Table 1.
3. Materials, construction and manufacturing methods
3.1 Conductor
The conductor shall be Rope-lay Stranded of annealed copper conductor. (Containing reinforcing member)
3.2 Insulation
The conductor shall be covered with heat resistant polyvinyl chloride, as insulation, concentrically in thickness shown in Attached Table 1.
Average thickness of the insulation shall not be less than 90% of value in Attached Tables.
Minimum thickness of the insulation shall not be less than 80% of value in Attached Tables.
3.3 Identification of cores
(1)4 or less conductors
The identification of cores shall be made by coloring of the insulation.
Insulation coloring
Black, White, Red, Green/Yellow
(2)5 or more conductors
Insulation is colored white and printed in Arabic numerals by blue ink.
Insulation numbering
Marking of 1,2,3,4,5, ·········
3.4 Assembly of cores
The insulated wires shall be arranged such as indicated in figure 1 and assembled, with fillers if necessary, and rolled up with tape on the assembly.
3.5 Sheath
Assembled cores shall be covered with oil and heat resistant polyvinyl chloride (black), concentrically in thickness shown in Attached Table 1.
Average thickness of the sheath shall not be less than 90% of value in Attached Tables.
Minimum thickness of the sheath shall not be less than 70% of value in Attached Tables.
Figure